ARE Fire Protection Cheat Sheet

Fire ratings by assembly type, fire barriers vs fire walls, sprinkler types, standpipe classes, and alarm types for the ARE 5.0 exam.

Fire Protection Quick Reference

This cheat sheet covers fire-rated assemblies, fire separation terminology, and active fire protection systems tested on the ARE 5.0 PDD exam. For in-depth study, see the Fire Protection topic guide.

Fire-Rated Separation Types

ElementRatingStructural IndependencePenetrationsContinuity
Fire wall2–4 hrYes (structurally independent)Very limitedFoundation to roof (or through roof)
Fire barrier1–4 hrNoThrough-penetration firestopFloor to floor/deck, wall to wall
Fire partition1 hr (typ.)NoThrough-penetration firestopFloor to ceiling or floor to deck
Smoke barrier1 hrNoLimited; smoke-tightContinuous from wall to wall, floor to floor
Smoke partition0 hrNoSmoke-tight at penetrationsFloor to ceiling
Shaft enclosure2 hr (≥4 stories) or 1 hr (<4 stories)NoFire-dampers at ductsContinuous vertical enclosure
Horizontal assembly1–2 hrNoThrough-penetration firestopFloor/ceiling assembly

Common Fire-Resistance Ratings

Assembly/SeparationTypical Rating
Occupancy separation (IBC Table 508.4)1–4 hr depending on occupancy pair
Corridor walls (sprinklered, >30 OL)0 hr or 1 hr (varies by occupancy)
Corridor walls (non-sprinklered, >30 OL)1 hr
Dwelling unit separation1 hr
Exit stair enclosure (≥4 stories)2 hr
Exit stair enclosure (<4 stories)1 hr
Exit passageway1–2 hr (matches stair enclosure)
Tenant separation1 hr (fire partition)
Area separation wall (townhouses)2 hr fire wall

Sprinkler Systems (NFPA 13)

TypeDescriptionApplication
Wet pipePipes filled with pressurized waterMost common; heated spaces
Dry pipePipes filled with pressurized air; water behind valveUnheated spaces (parking, loading docks)
Pre-actionDry pipe + supplemental detection required to open valveMuseums, data centers, archives
DelugeOpen heads; all activate simultaneouslyHigh-hazard: aircraft hangars, chemical plants
ESFREarly suppression, fast responseHigh-piled storage warehouses

Sprinkler Head Types

  • Pendant: Hangs from ceiling; most common in finished spaces
  • Upright: Points upward from exposed piping
  • Sidewall: Mounts on wall near ceiling; for corridors, small rooms
  • Concealed: Flush cover plate; for aesthetics in finished ceilings

Standpipe Classes

ClassHose ConnectionUsersTypical Location
Class I2-1/2" outletFire department onlyStairwells, high-rise buildings
Class II1-1/2" hose stationBuilding occupantsCorridor cabinets
Class IIIBoth 2-1/2" and 1-1/2"Both fire dept and occupantsStairwells in high-rise

When required: Buildings >3 stories, or where the highest floor is >30' above fire department access.

Fire Alarm & Detection Types

ComponentFunction
Smoke detector (ionization)Fast-flaming fires; particles disrupt ion current
Smoke detector (photoelectric)Smoldering fires; particles scatter light beam
Heat detector (fixed temp)Activates at set temperature (typically 135°F or 200°F)
Heat detector (rate-of-rise)Activates on rapid temperature increase (>12–15°F/min)
Manual pull stationNear exits, within 5' of exit doors, travel distance ≤200'
Fire alarm control panel (FACP)Central brain; monitors all devices, triggers notification
Notification appliancesHorns, strobes, speakers; must meet ADA requirements

Solidify your fire protection knowledge with PDD flashcards and PDD mini exams. Sign up free to track your progress.